Skip to main content

534 ThermoFill EA

  • Integrated ball valve and non-return valve
  • Classified as type EA according to EN 1717

534 ThermoFill EA is a filling valve for heating systems. The valve has an integrated shut-off/check valve which ­ensures opening even at low pressure differences. The check valve is inspectionable and classified as a back flow preventer Type EA, fluid category 1-2, according to EN 1717.

By closing the first valve towards the tap water system and loosening the screw, the function of the check valve can be checked.

The arrow on the valve body indicates the direction of the flow.

The thread has to be sealed in the usual manner.
It is easier to fit the compression fitting if a lubricant is applied to the thread and bevel. Tighten first by hand and then with a box spanner. Number of turns to be tightened with a spanner: See the separate datasheet for compression fittings. Soft pipes are to be fitted with a support sleeve.

The valve requires no maintenance but the installation should be checked regularly.

.

Technical Data

Max. working pressure: 1.0 MPa (10 bar)
Opening pressure, check valve: 1 kPa (0,01 bar)
Working temperature: Min. 5 °C/Max. 90 °C
Thread standard: G – female thread, ISO 228/1
Material, valve body: DZR Brass EN 12165 CW625N
Material, sealing: EPDM
Material, check valve: POM
Standard: Check valve: Type EA according to EN 1717

Documents